3412C (50 Hz)

3412C (50 Hz)

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Maximum Rating 900 kVA 900 kVA
Minimum Rating 680 kVA 680 kVA
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel Consumption

Technicial Specifications

Generator Set Specifications
Maximum Rating 900 kVA 900 kVA
Minimum Rating 680 kVA 680 kVA
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel Consumption
Voltage 380 to 415 Volts 380 to 415 Volts
Frequency 50 Hz 50 Hz
Speed 1500 rpm 1500 rpm
Duty Cycle Standby, Prime Standby, Prime
Engine Specifications
Engine Model 3412C TA, V-12, 4-Stroke Water-Cooled Diesel 3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore 5.4 in 137.2 mm
Stroke 6 in 152.4 mm
Displacement 1648.86 in³ 27.02 l
Compression Ratio 13:01 13:01
Aspiration TA TA
Fuel System Pump and Lines Pump and Lines
Governor Type ADEM™ A5 ADEM™ A5
Generator Set Dimensions
Length - Maximum 162.4 in 4125 mm
Width - Minimum 75 in 1906 mm
Width - Maximum 78.3 in 1989 mm
Height - Maximum 75 in 1906 mm
Dry Weight - Genset (minimum) 12039 lb 5461 kg
Dry Weight - Genset (maximum) 13030 lb 5910 kg

Advantages and Features

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR500 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • Eurasian Conformity (EAC)

One Safe Source

  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standard Equipment

  • Air Inlet System
    • Air cleaner, single element canister type with service indicator
  • Control Panel
    • EMCP 4.2B
    • Customer data link (Modbus RTU)
    • 2 Programmable relay outputs (Form C)
    • Features include:
    • Voltage adjust
    • Failure to start (overcrank)
    • Volts (L-L & L-N)
    • Reverse power (kW) (32)
    • Accessory module data link
    • Over/under voltage (27 / 59)
    • Speed adjust
    • Low coolant temperature
    • Oil pressure (psi, kPa or bar)
    • Environmental sealed front face
    • Generator temperature monitoring module
    • DC volts
    • Serial annunciator module data link
    • Reverse reactive power (kVAr) (32RV)
    • Amps (per phase & average)
    • High coolant temperature
    • 24 Volt DC operation
    • Communications
    • Power factor (per phase & average)
    • Compatible with the following optional modules:
    • Low coolant level
    • Text alarm/event descriptions
    • Digital I/O module
    • 6 programmable digital inputs
    • Low oil pressure
    • Remote Serial annunciator
    • Engine cycle crank
    • Local annunciator
    • Digital indication for:
    • Over/under frequency (81 o/u)
    • Generator phase sequence
    • Emergency stop
    • kVAr (per phase, average & percent)
    • Run/auto/ stop/control
    • Operating hours
    • kVA (per phase, average & percent)
    • Warning/shutdown with common LED indication of shutdowns for:
    • Emergency stop pushbutton
    • Frequency (Hz)
    • coolant temperature
    • Overspeed
    • 4 programmable relay outputs (Form A)
    • kW-hr (total)
    • 2 Programmable digital outputs
    • Remote CAN annunciator
    • Overcurrent (50 / 51)
    • kW (per phase, average & percent)
    • RPM
    • Programmable protective relaying functions:
  • Cooling System
    • Radiator with guard (Sized for 50 degrees C)
    • Coolant level shutdown
    • Coolant drain line with valve, piped to edge of base
    • Fan and belt guards
    • Caterpillar extended life coolant
  • Exhaust System
    • Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose
  • Fuel System
    • Primary and Secondary fuel filters
    • Fuel priming pump
    • Flexible fuel lines terminated on base
    • Water seperator
  • Generator and Attachments
    • 2:1 Volts/Hz
    • Busbar termination
    • 3-phase sensing
    • Class H insulation
    • Reactive droop
    • VR6 voltage regulator
    • SR4B self excited
    • 12 Leads
    • Class F temperature rise
  • Governing System
    • Cat electronic governor
  • Lube System
    • Oil drain line with valve, piped to edge of base
    • Lubricating oil
    • Oil filter
    • Fumes disposal, piped to front of radiator
  • Mounting System
    • Base, formed steel with linear vibration isolators between base and engine-generator
  • Starting / Charging System
    • 45 amp Charging alternator
    • Battery with rack, cables
    • Fuel shutoff solenoid
    • 24 volt starting motor

Optional Equipment

  • Air Inlet System
    • Heavy duty air cleaners
    • Dual element air cleaners
    • Open element air cleaners
  • Circuit breakers
    • 1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
    • 1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip
  • Control Panel
    • Generator temperature monitoring package
    • EMCP 4.4
    • First local annunicators
    • Vandal proof panel door
    • Remote custom annunicator
    • EMCP 4.3
    • Local discrete I/O package
    • Common alarm/shutdown relay
    • Ground fault relay
    • Generator running VFC
  • Cooling System
    • Radiator duct flange
    • Jacket water heaters
  • European Certifications
    • Eurasian Conformity (EAC) mark
  • Exhaust System
    • Through wall installation kit
    • Mufflers
    • Manifold and turbocharger guards
    • Elbow kit
  • Generator and Attachments
    • Permanent magnet excitation (PMG)
    • Space heater
    • Digital voltage regulator
    • Oversize and premium generators
  • Lube System
    • Manual sump pump
  • Mounting System
    • Fuel tank base (1200 ltr)
  • Special Tests / Reports
    • PGS Test report @ 0.8 power factor
    • PGS Test report @ 1.0 power factor
  • Starting / Charging
    • Oversize batteries
    • Battery chargers
    • Battery disconnect switch
    • Heavy duty starting system
  • Governing System
    • Electronic load share