Technicial Specifications
Maximum Rating | 550 kVA 550 kVA |
Minimum Rating | 550 kVA 550 kVA |
Emissions/Fuel Strategy | Non Regulated Non Regulated |
Voltage | 380 to 415 Volts 380 to 415 Volts |
Frequency | 50 Hz 50 Hz |
Speed | 1500 rpm 1500 rpm |
Duty Cycle | Standby Standby |
Engine Model | C13 In-line 6, 4-cycle diesel C13 In-line 6, 4-cycle diesel |
Bore | 5.1 in 130 mm |
Stroke | 6.2 in 157 mm |
Displacement | 763 in³ 12.5 l |
Compression Ratio | 15.8:1 15.8:1 |
Aspiration | Turbocharged Air-to-Air Aftercooled Turbocharged Air-to-Air Aftercooled |
Fuel System | EUI EUI |
Governor Type | Adem™A4 Adem™A4 |
Length - Maximum | 122 in 3100 mm |
Width - Maximum | 52.7 in 1338 mm |
Height - Maximum | 85.4 in 2168 mm |
Dry Weight - Genset (maximum) | 6693 lb 3036 kg |
Advantages and Features
Cat Generator Set Package
- Cat generator set packages have been fully prototype tested
- Accepts 100% block load in one step and meets NFPA 110 loading requirements
- Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
- Reliable, rugged, durable design
- Field-proven in thousands of applications worldwide
- Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
A-Frame Alternator
- Superior motor starting capability minimizes need for oversizing alternator
- Designed to match performance and output characteristics of Cat diesel engines
- Robust Class H insulation
GCCP 1.1 Control Panel
- User-friendly interface and navigation
- Scalable system to meet a wide range of installation requirement
- Expansion modules and site-specific programming for specific customer requirements
Cooling System
- Designed to operate in standard ambient temperatures up to 55°C (131°F)
- Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
- CE Certification Available
- CIS Certification Available
One Safe Source
- Components used in the generator set are selected based on seamless design integration to provide the optimum performance
- The generator set is fully assembled at a Caterpillar facility following our quality guidelines
- Each generator set package is tested before leaving the Caterpillar facility
- Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
- Cat dealers have over 1,800 dealer branch stores operating in 200 countries
- Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements
Standard Equipment
-
Engine
- Cat® C13 Inline 6 cylinder, 4 stroke diesel
-
Control Panels
- GCCP 1.1
-
Governor
- Mechanical governor
-
Alternator
- A Frame standard alternator
-
Fuel Storage
- Single wall 8 hour fuel tank
-
Cooling System
- Radiator and cooling fan with guards
- Fan drive, battery charging alternator drive
-
Electrical Options
- 3 Pole Circuit breaker
- Neutral earth link
- 24 Volt battery with rack and cables
-
Air inlet system
- Air cleaner; light duty with disposable element
-
Lube system
- Lubricating oil
- Oil drain line with valve
-
Mounting system
- Captive linear vibration isolators
- Lifting provision and drag points
-
Generator and Attachments
- Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
-
Packaged Generator Set
- Coolant drain line with valve
- Radiator package mounted
- Service indicator
- Low coolant level sensor
- Disposable air filter
- Coolant level sight gauge
-
Governing System
- Cat electronic governor (ADEM A4)
-
Lube System
- Oil drain valves
- Oil cooler
- Lubricating oil
-
Mounting System
- Captive linear vibration isolators between base and engine-generator
- Includes lifting provisions and termination points for coolant and lube oil drain lines
-
Starting / Charging System
- 24V battery with rack and cables
-
General
- Engine and alternator pre paint, Caterpillar yellow
- Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment
-
Control panel
- Speed and Voltage adjust potentiometers
- PLG 4G/3G/Ethernet
- Annunciator
- Emergency E-Stop
-
Enclosure
- Cat GC enclosure
-
Electrical Options
- 4 Pole Circuit breaker
- Auxiliary contacts
- Padlockable circuit breaker
- Battery charger
- Wet battery
-
Circuit breakers
- Circuit breaker (IEC) Auxiliary contacts
- Shunt trip for IEC circuit breaker
- 4 Pole (IEC-100% rated) Circuit breaker - Motorised
-
Alternator
- Space heater
- AVR
-
Fuel System
- Dual wall 8 hour fuel tank
- Single wall 8 hour fuel tank with spill containment
- Low fuel level shutdown
- Low and high fuel level alarms
- Manual fuel transfer pump
- Integral dual wall fuel tank base
- Fuel transfer system controls
-
Air inlet system
- Single stage air filter
- Dual element air filter
-
Certifications
- EU Certificate of Conformance (CE)
- EAC Certification
-
Extended service coverage
- 3, 4, 5 and 10 Years
-
Exhaust System
- Industrial silencer
- 10 dBA Attenuation silencer
- Flexible 8 inch exhaust fittings
- 10, 25 and 35 dBA attenuation
- 6 and 8 inch flange GP
- 6 and 8 inch elbow kit
-
Generator and Attachments
- A Frame oversize generator
- A Frame CIP generator
- Permanent magnet excitation (PMG) generator
- Ingress protection
- LC CIP generator
- LC frame generator
- Space heaters
-
Lube System
- Manual sump pump
-
Mounting System
- Narrow skid base
-
starting / Charging System
- 5 Amp single Battery charger
- Battery disconnect switch
- Jacket water heater