CG170-16

CG170-16

CG170 Gas Generator Set

Continuous Rating 1560 ekW @1.0pf 1560 ekW @1.0pf
Fuel Type Natural Gas, Biogas, Coal Gas Natural Gas, Biogas, Coal Gas
Maximum Electrical Efficiency 43.30% 43.30%

Technicial Specifications

Generator Set Specifications
Continuous Rating 1560 ekW @1.0pf 1560 ekW @1.0pf
Fuel Type Natural Gas, Biogas, Coal Gas Natural Gas, Biogas, Coal Gas
Maximum Electrical Efficiency 43.30% 43.30%
Frequency 50 or 60 Hz 50 or 60 Hz
RPM 1500 or 1800 rpm 1500 or 1800 rpm
Engine Specifications
Engine Model CG170-16 CG170-16
Displacement 4320 in³ 70.8 l
Aspiration TA TA
Bore 6.7 in 170 mm
Stroke 7.7 in 195 mm
Generator Set Dimensions
Length 261.4 in 6640 mm
Width 70 in 1778 mm
Height 87 in 2210 mm
Dry Weight - Genset 32848.5 lb 14900 kg

Advantages and Features

High Efficiency, Lower Operating Costs

  • Miller cycle timing with combustion chamber and spark plug improvement help on saving up to 15% fuel gas per year
  • CG170 (non-miller) is optimized for Island-Mode capability
  • Gearbox helps limit wear and tear on engine components, lowering operating costs and increasing availability

Low installation, Building and Operating Costs

  • Extended maintenance intervals thanks to sooth-free combustion and enlarged oil tank
  • Low fuel consumption due to improved combustion chamber and pre-chamber spark-plugs
  • Flexible fields of application also with fluctuating gas qualities due to Total Electronic Management (TEM)
  • Optimized oil management

Optimized Lubrication Consumption

  • Consumes up to 1900 liter less lube oil per year than comparable models<\li>
  • Longer lubricant change and oil change intervals<\li>

Standard Equipment

  • Air Inlet
    • Turbocharger with a water-cooled bearing case for all cylinder
    • One-element single-stage air cleaner with enclosure and sevice indicator
  • Control Panels
    • TEM (Total Electronic Management)
  • Cooling
    • Jacket water and SCAC thermostats
    • Electrical jacket water and aftercooler coolant pump
    • flange connections for JW inlet and outlet
    • Cat flanges on SCAC circuit
  • Exhaust
    • PEARL/Low resistence exhaust system
    • Closed crankcase ventilation system
  • Fuel system
    • Independently controlled cylinder monitoring and ignition system
    • Pre-chamber spark plugs
    • Electronic fuel metering valve
  • Generator
    • Busbar connections
    • Anti-condensation space heater
    • closed-coupled generator result in no torque transmission to the base frame
    • Winding temperature detectors
    • Reactive droop
    • 3-phase sensing and KVAR/PF control
    • grid code generator
  • Starting/Charging
    • 24V starting motors
    • Battery disconnect switch
  • General
    • Crankshaft vibration damper and guard

Optional Equipment

  • Air Inlet
    • Mounting stand
    • Air cleaner with precleaner
  • Cooling
    • CHP skid
  • Grid Code Compliance
    • 50Hz: Germany, Belgium, Great Britain, Italy, Poland, and Netherlands