3512 (50 Hz)

3512 (50 Hz)

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Standby Rating 1400/1250 kVA 1400/1250 kVA
Prime Power Rating 1275/1150 kVA 1275/1150 kVA
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel Consumption

Teknik Özellikler

Generator Set Specifications
Standby Rating 1400/1250 kVA 1400/1250 kVA
Prime Power Rating 1275/1150 kVA 1275/1150 kVA
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel Consumption
Voltage 380 to 415 Volts 380 to 415 Volts
Frequency 50 Hz 50 Hz
Speed 1500 rpm 1500 rpm
Duty Cycle Standby, Mission Critical, Prime, Continuous Standby, Mission Critical, Prime, Continuous
Maximum Rating 1400 kVA 1400 kVA
Minimum Rating 1000 kVA 1000 kVA
Engine Specifications
Engine Model 3512 TA, V-12, 4-Stroke Water-Cooled Diesel 3512 TA, V-12, 4-Stroke Water-Cooled Diesel
Bore 6.69 in 170 mm
Stroke 7.48 in 190 mm
Displacement 3161.03 in³ 51.8 l
Compression Ratio 13.5:1 13.5:1
Aspiration TA TA
Fuel System Direct Unit Injection Direct Unit Injection
Governor Type Woodward Woodward
Generator Set Dimensions
Length - Minimum 202.7 in 5149 mm
Length - Maximum 206.6 in 5249 mm
Width - Maximum 77.8 in 1975 mm
Height - Maximum 93.2 in 2367 mm
Dry Weight - Genset (minimum) 22650 lb 10270 kg
Dry Weight - Genset (maximum) 23170 lb 10510 kg

Avantaj ve Özellikler

Cat Generator Set Package

  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine

  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator

  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel

  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System

  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications

  • Telecom Lab of China (TLC)
  • EU Declaration of Conformity
  • EU Declaration of Incorporation
  • Eurasian Conformity

One Safe Source

  • Components used in the generator set are selected at the design stage to provide optimum package performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

Worldwide Product Support

  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Standart Donanımlar

  • Air Inlet System
    • Air cleaner; single element canister type with service indicator
  • Control Panel
    • EMCP4.2B controls includes: Emergency stop pushbutton
    • RPM
    • Engine cool-down timer
    • EMCP4.2B controller includes:
    • Accessory module data link
    • 4 programmable relay outputs (Form A)
    • Communications:
    • Volts (L-L & L-N)
    • Over/under frequency (81 o / u)
    • Text alarm/event descriptions
    • Auto/start/stop control
    • Speed adjust
    • kVA (per phase, average & percent)
    • Overcurrent (50 / 51)
    • Alarm acknowledge
    • Environmental sealed front face
    • 6 programmable digital inputs
    • Oil pressure (psi, kPa or bar)
    • Amps (per phase & average)
    • Generator phase sequence
    • 2 Programmable digital outputs
    • Low coolant temperature
    • Controls:
    • Serial annunciator module data link
    • Reverse power (kW) (32)
    • Lamp test
    • Coolant temperature
    • Engine cycle crank
    • kVAr-hr (total)
    • 2 Programmable relay outputs (Form C)
    • Generator mounted - rear facing
    • 24 Volt DC operation
    • kVAr (per phase, average & percent)
    • Warning/shutdown with common LED indication of shutdowns for:
    • kW (per phase, average & percent)
    • Reverse reactive power (kVAr) (32RV)
    • Programmable protective relaying functions:
    • Digital indication for:
    • High coolant temperature
    • Low oil pressure
    • Overspeed
    • Over/under voltage (27 / 59)
    • Customer data link (Modbus RTU)
    • DC volts
    • Operating hours
    • Low coolant level
    • kW-hr (total)
    • Frequency (Hz)
    • Emergency stop
    • Power factor (per phase & average)
    • Failure to start (overcrank)
    • True RMS AC metering, 3-phase, +/-2% accuracy
  • Cooling System
    • JWAC
    • Caterpillar extended life coolant. (Not included with packages without radiator, installed SF44CTS, shipped loose radiators or heat exchangers)
    • Radiator fan and fan drive
    • Fan and belt guards
    • Coolant drain line with valve
    • Coolant level sensors (Not included with packages without radiator)
  • Exhaust System
    • Dry exhaust manifold
    • Flanged faced outlet(s)
  • Fuel System
    • Fuel cooler; not included with packages without radiator
    • Flexible fuel lines - shipped loose
    • Fuel priming pump
    • Secondary fuel filters
  • Generators and Attachments
    • Generator set packages include: Regulator (CDVR)
    • 6 Lead
    • Min / max exciter limiter
    • LV
    • Reactive droop capability
    • Random wound
    • Exciter diode monitor
    • KVAR/PF modes
    • NEMA Class H insulation
    • 50 Hz models: IEC standard hole pattern
    • Caterpillar's digital voltage regulator (CDVR) includes:
    • Note: 1800 Frames are form wound, permanent magnet excitation (PMG), with winding temp detectors
    • Busbar connections, top center mounted, top cable entry
    • Internal excitation (IE)
    • Winding temperature detectors
    • Class H temperature rise at 40C ambient (125C prime/150C standby)
    • 3 Phase brushless, Salient pole
    • 3 Phase voltage sensing
    • RFI suppression
  • Governing System
    • Woodward 2301A isochronous governor
  • Lube System
    • Oil drain lines and valve
    • Gear type lube oil pump
    • Fumes disposal
    • Oil filter, filler and dipstick
    • Lubricating oil
    • Integral lube Oil cooler
  • Mounting System
    • Rubber anti-vibration mounts - shipped loose
    • Rails - engine/generator/radiator mounting
  • Starting / Charging System
    • 24 Volt electric starting motor
    • Battery and battery rack w/cables
    • Battery disconnect switch
  • General
    • Paint - Caterpillar yellow with high gloss black rails & radiator
    • SAE standard rotation
    • RH service
    • Flywheel and Flywheel housing - SAE No. 00

İsteğe Bağlı Donanımlar

  • Air Inlet System
    • Remote air inlet adaptors
    • Air inlet protection
    • Dual element air cleaners
  • Circuit breakers
    • EMAX Circuit breakers
    • Center posts busbars
    • EMAX breakers connections
    • Breaker harnesses
    • 2000, 2500, 3200 and 4000 Amp, 4 pole, IEC rated Circuit breakers
    • Controls packaging - Enclosures
    • Cable entry options
    • 2000, 2500, 3200 and 4000 Amp, 3 pole, IEC rated Circuit breakers
    • Optional busbar power connections
    • Busbar connections
  • Control Panel
    • Auxiliary boxes
    • Customer connection mounting locations
    • Ground (Automatically selected)
    • Vandle proof panel door
    • Customer Interface options
    • Mounting group - External box clips
    • Remote speed adjust
    • Generator temperature monitoring
    • Governors
    • Annunciator Modules
    • Local PC monitoring
  • Cooling System
    • Water level switch gauges
    • Heat exchangers
    • Optional radiator arrangements
  • European Certifications
    • EU Declaration of Conformity
    • Eurasian Conformity (EAC) mark
    • European Directive genset, DoI (Declaration of Incorporation)
    • European Union Certification
  • Exhaust System
    • Through-wall installation kit
    • Muffler mounting kits
    • Mufflers
    • Flexible fittings
  • Fuel System
    • Primary fuel filter
  • Generators and Attachments
    • 380 / 400 / 415 Volts @ 50 Hz, 3 phase, Form wound, Permanent magnet excitation (PMG), No. of leads = 6, pitch= 0.6667
    • 380/400/415volts @ 50 Hz, 3 phase, random wound, Permanent magnet excitation (PMG), No. of leads = 6, pitch= 0.6667
    • Generator conversion
    • 380/400/415volts @ 50 Hz, 3 phase, random wound, Internal excitation (IE), No. of leads = 6, pitch= 0.6667
    • Space heater
  • Instrumentation
    • Pyrometer and thermocouples
  • Lube System
    • Electric prelube pumps
    • Oil level reg-1 shallow pan
    • Manual prelube sump pumps
  • Mounting System
    • Spring type vibration isolators
    • IBC vibration isolators
  • Protection System
    • Explosion relief valves
  • Special Tests / Reports
    • Neutral grounding connection
    • IBC seismic Certifications
    • Neutral ground-LV
    • PGS Test report @ 1.0 power factor
    • PGS Test report @ 0.8 power factor
  • Starting / Charging Systems
    • Ether starting aid
    • 24 Volt dual electric starting motor
    • 20 Amp Battery charger
    • Oversize battery set
    • Jacket water heaters
    • 10 Amp Battery chargers
  • General
    • Engine barring group